** Warning ** GetSpecificHeatGlycol: Temperature is out of range (too high) for fluid [WATER] specific heat **
** ~~~ ** ..Called From:PlantLoopSolver::UpdateAnyLoopDemandAlterations,Temperature=[489.11], supplied data range=[0.00,125.00]
** ~~~ ** Environment=RUN PERIOD 1, at Simulation time=02/21 09:15 - 09:30
** Severe ** Plant temperatures are getting far too hot, check controls and relative loads and capacities
** ~~~ ** Environment=RUN PERIOD 1, at Simulation time=02/21 09:15 - 09:30
** ~~~ ** PlantLoop Name (DemandSide)= CONDENSER WATER PLANT
** ~~~ ** PlantLoop Setpoint Temperature=24.0 {C}
** ~~~ ** PlantLoop Inlet Node (SupplySide) does not have a Setpoint.
** ~~~ ** PlantLoop Inlet Node (DemandSide) does not have a Setpoint.
** ~~~ ** PlantLoop Outlet Node (SupplySide) has a Setpoint.
** ~~~ ** PlantLoop Outlet Node (DemandSide) does not have a Setpoint.
** ~~~ ** PlantLoop Outlet Node (DemandSide) "NODE 31" has temperature=965.6 {C}
** ~~~ ** PlantLoop Inlet Node (DemandSide) "NODE 30" has temperature=12.5 {C}
** ~~~ ** PlantLoop Minimum Temperature=0.0 {C}
** ~~~ ** PlantLoop Maximum Temperature=100.0 {C}
** ~~~ ** PlantLoop Flow Request (SupplySide)=0.0 {kg/s}
** ~~~ ** PlantLoop Flow Request (DemandSide)=4.7E-005 {kg/s}
** ~~~ ** PlantLoop Node (DemandSide) "NODE 31" has mass flow rate =4.7E-005 {kg/s}
** ~~~ ** PlantLoop PumpHeat (SupplySide)=1.1E-002 {W}
** ~~~ ** PlantLoop PumpHeat (DemandSide)=0.0 {W}
** ~~~ ** PlantLoop Cooling Demand=0.0 {W}
** ~~~ ** PlantLoop Heating Demand=3.8 {W}
** ~~~ ** PlantLoop Demand not Dispatched=0.0 {W}
** ~~~ ** PlantLoop Unmet Demand=3.5 {W}
** ~~~ ** PlantLoop Capacity=95840.3 {W}
** ~~~ ** PlantLoop Capacity (SupplySide)=95840.3 {W}
** ~~~ ** PlantLoop Capacity (DemandSide)=0.0 {W}
** ~~~ ** PlantLoop Operation Scheme=CONDENSER WATER PLANT OPERATION SCHEMES
** ~~~ ** PlantLoop Operation Dispatched Load = 47821.1 {W}
** ~~~ ** PlantLoop Operation Dispatched Load (SupplySide)= 47821.1 {W}
** ~~~ ** PlantLoop Operation Dispatched Load (DemandSide)= 0.0 {W}
** ~~~ ** Branches on the Loop.
** ~~~ ** Demand Branches:
** ~~~ ** CONDENSER WATER PLANT DEMAND INLET BRANCH
** ~~~ ** Components on Branch:
** ~~~ ** PIPE:ADIABATIC:CONDENSER WATER PLANT DEMAND INLET PIPE
** ~~~ ** CONDENSER WATER PLANT DEMAND BRANCH 1
** ~~~ ** Components on Branch:
** ~~~ ** COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT:COIL HEATING WATER TO AIR HEAT PUMP EQUATION FIT 1
** ~~~ ** CONDENSER WATER PLANT DEMAND BRANCH 2
** ~~~ ** Components on Branch:
** ~~~ ** COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT:COIL COOLING WATER TO AIR HEAT PUMP EQUATION FIT 1
** ~~~ ** CONDENSER WATER PLANT DEMAND BYPASS BRANCH
** ~~~ ** Components on Branch:
** ~~~ ** PIPE:ADIABATIC:CONDENSER WATER PLANT DEMAND BYPASS PIPE
** ~~~ ** CONDENSER WATER PLANT DEMAND OUTLET BRANCH
** ~~~ ** Components on Branch:
** ~~~ ** PIPE:ADIABATIC:CONDENSER WATER PLANT DEMAND OUTLET PIPE
** ~~~ ** Supply Branches:
** ~~~ ** CONDENSER WATER PLANT SUPPLY INLET BRANCH
** ~~~ ** Components on Branch:
** ~~~ ** PUMP:VARIABLESPEED:PUMP VARIABLE SPEED 2
** ~~~ ** CONDENSER WATER PLANT SUPPLY BRANCH 1
** ~~~ ** Components on Branch:
** ~~~ ** DISTRICTHEATING:DISTRICT HEATING 1
** ~~~ ** CONDENSER WATER PLANT SUPPLY BRANCH 2
** ~~~ ** Components on Branch:
** ~~~ ** EVAPORATIVEFLUIDCOOLER:SINGLESPEED:EVAPORATIVE FLUID COOLER SINGLE SPEED 1
** ~~~ ** CONDENSER WATER PLANT SUPPLY BRANCH 3
** ~~~ ** Components on Branch:
** ~~~ ** GROUNDHEATEXCHANGER:SYSTEM:GROUND HEAT EXCHANGER VERTICAL 1
** ~~~ ** CONDENSER WATER PLANT SUPPLY BRANCH 4
** ~~~ ** Components on Branch:
** ~~~ ** PIPE:ADIABATIC:PIPE ADIABATIC 3
** ~~~ ** CONDENSER WATER PLANT SUPPLY OUTLET BRANCH
** ~~~ ** Components on Branch:
** ~~~ ** PIPE:ADIABATIC:PIPE ADIABATIC 4
** ~~~ ** *************************
** ~~~ ** Possible things to look for to correct this problem are:
** ~~~ ** Capacity, Operation Scheme, Mass flow problems, Pump Heat building up over time.
** ~~~ ** Try a shorter runperiod to stop before it fatals and look at
** ~~~ ** lots of node time series data to see what is going wrong.
** ~~~ ** If this is happening during Warmup, you can use Output:Diagnostics,ReportDuringWarmup;
** ~~~ ** This is detected at the loop level, but the typical problems are in the components.
** Fatal ** CheckForRunawayPlantTemps: Simulation terminated because of run away plant temperatures, too hot
...Summary of Errors that led to program termination:
..... Reference severe error count=1
..... Last severe error=Plant temperatures are getting far too hot, check controls and relative loads and capacities